Technical Data
Switch temperature difference | 7K (±4K tolerance) |
Sensor element | thermostatic bimetal |
Contact type | snap-action contact |
Contact resistance | < 10mΩ |
Service life | > 100,000 cycles |
Max. Switching capacity | 250VAC, 10 (2) A 120VAC, 15 (2) A DC 30W |
EMC | acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 |
Connection | 4-pole terminal,clamping torque 0.5Nm max. rigid wire 2.5mm²stranded wire (with wire end ferrule) 1.5mm² |
Mounting | clip for 35mm DIN rail,EN60715 or for exit filter EF 118 Series |
Casing | plastic according to V-0, light grey |
Dimensions | 60 x 33 x 43mm |
Weight | approx. 40g |
Installation position | variable |
Operating/Storage temperature | -20 to+80℃(-4 to +176 ) /-45 to+80 (-49 to +176 ) |
Protection type | IP20 |