Temperature and humidity adjustable
Optical operating display (LED)
High switching capacity
DIN rail mounted
The electronic hygrotherm senses the ambient temperature and relative humidity in an enclosure with electric/electronic components and turns on a heater(or alterna- tively a fan)at either set point,helping prevent the formation of condensation in the enclosure.Due to its wide voltage range the hygrotherm can be utilised anywhere in the world The LED integrated in the adjustment knob on the active controller is lit when the connected device is in operation
Switch temperature difference | 2K (±1K tolerance)at 2S°Cm°V (50% RH) |
Switch difference(humidity) | 4% RH ( ± 1% tolerance) at 25°C /770 F (50% RH) |
Reaction time (humidity) | approx. 5 sec. |
Contact type | change-over contact (relay) |
Contact resistance | < 10mQ |
Service life | NC: > 50,000 cycles |
NO: > 100,000 cycles | |
Max. Switching capacity(Relay output) | NC: 240VAC, 6(1) A NO: 240VAC, 8 (1.6) A |
NC: 120VAC, 6(1) A NO: 120VAC, 8(1.6) A | |
24VDC,4A | |
EMC | acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3 |
Optical indicator | LED |
Connection | 5-pole terminal,damping torque 0.5Nm max.:rigid yvire 2.5mm2 stranded wire (with wire end ferrule) 1.5mm’ |
Mounting | clip for 35mm DIN rail,EN6075 or for exit filter EF 118 Series |
Casing | plastic according to UL94 V-0, light grey |
Dimensions | 77 x 60 x 43mm |
Weight | approx. 0.20kg |
Installation position | vertical |
Operating/Storage temperature | 0 to +60°C (+32 to +140° F ) / -20 to +80°C (-4 to +176° F) |
Protection type | IP20 |
Art.No | Operating voltage |
01230.0-00 | 230VAC,50/60HZ(min.90VAC,max.265VAC) |
01230.9-00 | 120VAC,50/60HZ(min.90VAC,max.265VAC) |
01230.9-01 | 120VAC,50/60HZ(min.20VAC,max.60VAC) |